AnotherGoodName ◴[] No.44360099[source]
Reads very similar to some blackouts we had in Australia. Weakly connected grids with vast geographical distances leading to oscillations that took down the grid.

https://en.wikipedia.org/wiki/2016_South_Australian_blackout

Completely solved with lithium based grid storage at key locations btw. This grid storage has also been massively profitable for it's owners https://en.wikipedia.org/wiki/Hornsdale_Power_Reserve#Revenu...

Australia currently has 4 of the 5 largest battery storage systems under construction as a result of this profit opportunity; https://en.wikipedia.org/wiki/Battery_energy_storage_system#...

You can also read numerous stories of how Australia's lithium ion grid storage systems have prevented blackouts in many cases. https://www.teslarati.com/tesla-big-battery-south-australia-... The fact is that the batteries responsiveness is the fastest of any system at correcting gaps like this. 50/60hz is nothing for a lithium ion battery nor are brief periods of multi-gigawatt draw/dumping as needed.

There's even articles that if Europe investing in battery storage systems like Australia they'd have avoided this. https://reneweconomy.com.au/no-batteries-no-flexibility-spai...

replies(3): >>44360187 #>>44361587 #>>44363406 #
londons_explore ◴[] No.44360187[source]
> nor are brief periods of multi-gigawatt draw/dumping as needed.

Actually this is typically an issue for grid batteries.

Spinning generators can easily briefly go to 10x the rated current for a second or so to smooth out big anomalies.

Stationary batteries inverters can't do 10x current spikes ever - the max they can get to is more like 1.2x for a few seconds.

That means you end up needing a lot of batteries to provide the same spinning reserve as one regular power station.

replies(6): >>44360272 #>>44360408 #>>44360936 #>>44361327 #>>44362342 #>>44364686 #
1. pjc50 ◴[] No.44364686[source]
> Spinning generators can easily briefly go to 10x the rated current for a second or so to smooth out big anomalies.

I'm very suspicious of this, because it would also imply 10x overcurrent on the associated transmission gear. There's limits on how much you can overcurrent a transformer before the core magnetically saturates, for example. Also I would expect protection systems to trip out at such a huge divergence from rated current. Do we have a citation?